Table of Studies on Structures with Energy-Dissipating Fuses


System Information

Reference Description of System Frame Configuration Experiment Synopsis Purpose of Research
Aliaari and Memari 2007 Seismic infill wall isolator subframe (SIWIS) system used to prevent damage to columns or infill walls due to a sacrificial structural fuse The steel frame with brick masonry infill walls was designed with pinned beam-to-column and column-to-column connections In-plane lateral load testing of a scaled (1:4) 2-bay 3-story steel frame and a series of component tests on three different fuse element designs were performed Experimentally test the potential of the SIWIS system for the development of an effective way to reduce earthquake damage in framed buildings with infill walls
Bozorgzadeh et al. 2008 Shear keys in bridge abutments designed to provide transverse support to bridge superstructure Smooth construction joints at shear keys and minimizing the reinforcement between abutment and shear key allows dissipation of energy through sliding shear failure 10 Shear keys, in sets of 2 and having varying designs, were tested for their ability to reduce input force to abutment piles through means of sliding shear failure Reevaluate design equations for estimating capacity of shear keys, provide data to develop an analytical model of shear key capacity, and detail reinforcement and construction joint surface preparation at the interface of shear key-stem wall
Calado, Proenca, Espinha, and Castigloni 2013 A steel fuse located in a gap in the concrete slab of a beam to column subassembly to dissipate energy and prevent concrete fracture. A beam to column subassembly of a composite beam and a reinforced concrete slab. The subassemblies with the steel fuse were tested under cyclic and monotonic loading and the fuse behavior indicated high ductility, energy dissipation, and repairability. To experimentally test the proposed fuse device in a subassembly under seismic loading.
Chen, Su, and Tang 2011 A three-pin steel damper is designed for energy dissipation through damping rather than inelastic behavior of primary structural members Damper can be installed on a separated wall within a panel in a steel MRF The damper unit was tested for strength and displacement and an analytical model was created based on the results Evaluate if the proposed damping system is a feasible alternative for seismic resisting systems
Crisafulli and Restrepo 2003 Precast concrete walls with energy-dissipating embedded ductile perforated steel plates Welded steel plate connections for precast concrete elements Study behavior of isolated connecting plates, develop response design equations, and test reduced scale specimen with proposed connection detail Investigate connections for precast concrete elements under seismic events for low to medium rise buildings
Dicleli and Mehta 2009 Seismic retrofitted chevron-braced frame (RCBF) with a hysteretic energy-dissipating element installed between the braces and the connected beam Chevron type retrofit bracing for a concentrically braced frame The RCBF is presented and examined analytically and details of the retrofitting method are given Validate proposed RCBF for energy-dissipating capabilities and compare to conventional CBF performance
Farrokhi, Danesh, and Eshghi 2009 Cover plate type moment resisting connections with drilled holes Steel MRF with reduced plate section in the beam to column connections Test proposed moment resisting connections under cyclic nonlinear finite element analyses on numeric models and experimentally using full scale models Propose effective solution to reduce stress concentration at the weld roots by means of reducing the section of the beam or the connector elements
Filipov et al. 2011 Bridge system employing quasi-isolation by using a set of fixed bearings in addition to isolation bearings System uses stiffened L-shaped retainer brackets that limit transverse displacement of elastomeric bearings, so that the bridge responds elastically under service loading with certain bridge bearing components fusing under large seismic events A computational system analyses is performed for the described bridge system as well as modeling of the nonlinear behaviors of the substructure pier elements, bridge foundations and abutment back walls A parametric study of the conceptual model is being investigated for various bridge structures and bearing combinations to develop further design strategies
Fortney, Shahrooz, and Rassati 2007 Wall pier-coupling beam subassembly fitted with a steel coupling beam (SCB) and a SCB with an additional feature consisting of a central fuse system labeled as a fuse coupling beam (FCB) Outer beam sections are embedded in the wall piers using same design as a typical SCB and an energy-dissipating fuse connection is located at the central beam connection Full scale tested on SCB for low-rise steel buildings were performed Enhance features of steel coupling beams by providing post-damage replacement capabilities without costly repair
Gray, Christopoulos, and Packer 2010 Cast steel yielding fuse (CSF) using inelastic flexural yielding of specially design yielding elements of the cast connector Energy dissipation system for concentrically brace frames The cast connector concept is introduced, the cast steel material used for a device prototype is discussed and finally full-scale proof-of concept laboratory test results are presented Present the feasibility of a CSF device to eliminate the cyclic tensile yielding and inelastic compressive buckling of traditional braces
He, Chen, Eatherton and Shao 2018 An asymmetrical moment-resisting connection that concentrates damage in replaceable angles in order to achieve a repairable connection despite the presence of a concrete slab. Structural fuse elements connect an interior beam segment, with asymmetric angles on the bottom flange, to a beam stub rigidly attached to a column. Cyclic tests were conducted on sub-assemblies with differing angles. Verify the performance of a replaceable connection compatible with a composite concrete slab.
Iqbal 2006 Soft first story for multi-story structures with a seismic elastoplastic isolation system composed of Teflon-stainless steel sliding bearings and steel dampers assembled in a single device Sliding bearings carry primarily vertical load and dissipate energy through friction, while steel dampers provide the majority of energy dissipation No analytical or experimental studies were directly preformed Present and review energy-dissipating systems with varying shapes and arrangements from previous research for feasibility
Karydakis, Ionnides, and Vagias 2011 The Innovative Stiffness and Energy Dissipation System (INSTED) is composed of two vertical strong columns, which remain elastic, and expandable horizontal connections for energy dissipation through plastic hinging Anti-diagonal bracing in MRFs are replaced by vertical composite beams composed of two strong columns of square hollow section which are joined by horizontal beams in a tight arrangement Several test were run on varying connecting elements for their capability to dissipate energy and an analytical model was developed to compare the results; also the final design proposal was detailed The paper presents continuing work on the INSTED system with goal of providing experimental and analytical conformation of the seismic energy dissipation abilities for multi-story MRF buildings
Kasai et al. 2010 Full scale experimental testing of a steel frame with varying dampers 5-Story steel MRF examined with a steel, oil, viscous, and viscoelastic damper system Full scale shake table testing on the E-Defense table in Japan based on previous analytical modeling and damper component test Validate the reliability of the passive control technology through realistic experiments and compare to MRF without damping system
Kassis and Tremblay 2008 Novel brace fuse system consisting of rectangular or square fuse systems for typical single story structures Low-rise steel buildings and tall single story buildings Brace slenderness on capacity design force is reviewed, a brace fuse system is proposed, results from specimen test are discussed, and results from a parametric study of system benefits are examined A detailed braced fuse is presented and tested for its ability to reduce tension forces and maintain stable hysteretic response to seismic excitation
Ke, Chen, Zhou, Yam, Hu, 2023 A new brace-type hybrid damper (BTHD) with steel slit plates that utilizes one of two friction mechanisms: “frictional-metallic (FM)” and “metallic-frictional (MF)” The BTHD includes steel plate with two rows of slits and slotted holes with bolts to connect to sliding cover plates, and is connected to outer-fixure through anchorage plates. Performing both experimental and numerical analyses on the proposed dampers and compare the effect of energy dissipation sequence on overall performance. To develop a novel brace-type hybrid damper that utilizes friction mechanism that exhibits improved ductility and energy dissipation capacity.
Kim, Choi, and Min 2010 Rotational friction dampers connected to high strength tendons to enhance both seismic and progressive collapse-resisting capacity of existing structures Seismic retrofit of mid to high level rise reinforced concrete moment frames Present the performance of fiction dampers connected to high strength tendons and numerically analyze 3,6 and 15-story reinforced concrete moment frames fitted with dampers Evaluate the performance of the proposed energy dissipation system against seismic loads and their seismic and progressive collapse resisting capacity
Krstulovic–Opara and Nau 2003 Members combining conventional “passive” high-performance fiber reinforced concrete (HPFRCs) with “self-pre-stressing” shape memory alloy (SMAs) Self-actuating composite members designed to adjust their load-displacement response to seismic excitations, provide energy absorbing zones, and be replaceable after an earthquake Proposed design is evaluated using numerical simulation with plans of future detailed experimental investigations Explore validity of “self-actuating” HPFRC fuse concept and determine whether sufficiently high increase in fuse response can be achieved
Legeron, Desjardins, and Ahmed, 2014 Concentrically braced frames equipped with ductile fuses on the X bracing. Cross bracing connected through bolted gusset plate connections with fuses at the connections. Cyclic loading was applied to cross bracing with different fuse configurations. The fuse system decreased the compressional capacity of the system, but also increased the tensile strength of the system at the connections of the braces. To experimentally validate the use of steel fuses to increase energy dissipation of concentrically braced frames.
Lin, Chen, Yan, and Hu, 2020 High-strength steel was used to create the beams and columns in order to maximize elasticity of the members. The beam and column form a T joint with a welded connection. At the beam- column interface within the frame, a replaceable damage- control fuse is inserted to diffuse seismic energy. A welded T joint was used as the beam-column connection. A fuse was installed into this interface in order to prevent seismic energy from fracturing the welding. Experimentally determine if the fuses are a viable option in high-strength frames by subjecting this joint to displacement- controlled cyclic loading. It was found that the control specimen without fuses experienced fractures at the welding, while the specimen with fuses experienced deformation within the fuses, which could be replaced after an earthquake, making fuses a more economical and viable option for energy dissipation. Determine the functionality of fuses in a high-strength steel structure, and which type of fuse is more effective at dissipating seismic energy within the system.
MacRae 2008 Sliding hinge joint (SHJ) located at connections and Double Surface Friction Dissipaters (DSFD) located within bracing Sliding hinge joint (SHJ) located at connections and Double Surface Friction Dissipaters (DSFD) located within bracing Sliding hinge joint (SHJ) located at connections and Double Surface Friction Dissipaters (DSFD) located within bracing Sliding hinge joint (SHJ) located at connections and Double Surface Friction Dissipaters (DSFD) located within bracing
Mansour, Christopoulo, and Tremblay 2011 Eccentrically Brace Frame configuration with ductile replaceable shear links which are decoupled from the structural members Replaceable links located within floor beams, between eccentric braces for a steel frame Component test on two types of links and full scale global performance of the new EBF assembly were conducted and examined Assess an alternative to conventional EBF with a replaceable shear link providing advanced seismic performance, economic advantages, and extended building lifespan
Milani, Dicleli, 2022 Torsional Hysteretic Damper for Frames (THDF) that includes cylindrical ductile steel yielding elements (CYEs), a sliding block and a rotating arm that converts translational load into torque-twist response. 1/3rd-scale Chevron braced frame of a two stories structure, and 50-ton reaction frame with THDF placed between floor beam and inverted-V braces. Numerical and experimental analyses were carried out on the new THDF device with its adaptive post-elastic stiffness property to observe the force-displacement relationship and its effect on story drifts when subjected to seismic loads. To verify the seismic performance of the proposed THDF device that is specifically designed to have promising height-wise distribution and minimize drift concentration in multi-story buildings.
Ozaki, Kawai, Kanno, and Hanya, 2012 Steel plate with slits between a rocking frame, connected to a channel to the upper frame and bolted to the foundation. The steel frame with multiple slits acts as a fuse, and the shape of the fuse is in a butterfly pattern of steel plates welded to a U shaped steel channel. A shear wall system is connected to the hold down with fuse funcition. The shear wall system consists of corrugated steel sheets connected to a channel with self-drilling screws. The structure is one story and is made with two parallel shear walls and perpendicular steel braces connected with steel gusset planks. Experimentally determine the effectiveness of hold downs equipped with a fuse function using a shake table test. The experiment used one story, one span, real sized specimen and tested four separate structures, two different HDFs with different yield strengths, an elastic fastener with no fuse, and a free rocking structure with no hold downs. The structures were first tested with a static load test, then a shake table test, and their responses were observed. Research had been previously performed to test the effectiveness of HDFs using a static loading test and dynamic response analysis, but no shake table tests have been performed.
Ozaki, Kawai, Tanaka, Okada and Kanno 2010 A rocking steel shear wall system with replaceable energy dissipating fuses placed at the base connecting an anchor bolt and the steel sheet wall. A fuse panel with bisymmetric plural rhomboid slits having a butterfly shape is connected to a fitting steel channel by a slot weld. Two panels face each other and are inserted an inner hollow space of the steel channel and attached to the shear wall. Compares the energy dissipation between steel fuse panels with butterfly shapes and rhomboid slits and rectangular shapes and rectangular slits. Verify the seismic performance of the hold down fastener equipped with fuse function (HDFF).
Patro and Sinha 2008 Analytical analysis of a 4-story frame building with friction devices Multi-degree-of-freedom frame structure with friction slider mounted on the chevron brace Analyze frame through two phases: non-sliding wherein the frictional resistance between floor and device has not been overcome and sliding or slip phase Evaluate various dimensionless performance indices and optimal seismic performance of friction devices
Qu, Liu, Hou, and Qiu 2018 Buckling-restrained braces (BRB) fixed with a steel angle fuse. The frame is composed of three main components: an inner buckling-restraining mechanism (BRM), an outer BRM, and a buckling- restraining angle fuse. The specimen B0 failed under application of cyclic loading. Each of the subsequent specimens performed similarly to ordinary buckling- restrained braces. Slip deformations were exhibited in the bolted connections of the specimens, which absorbed 15% more hysteretic energy without affecting the strength. The purpose of this research is to experimentally compare a system with buckling-restrained braces to previously used concentrically braced frames.
Rai and Wallace 1998 An aluminium beam shear-link which yields in shear mode to limit maximum later force in earthquake resistant systems I-shaped aluminium beam is place between the tops of the diagonal braces and a floor beam from the story above The link was tested with varying parameters to determine energy dissipating capabilities and an analytical model was created to compare seismic performance to an ordinary CBF Describe the inelastic cyclic behavior of the shear-link and its role as a seismic energy dissipater in a bracing frame structural system
Ruangrassamee and Mounnarath 2008 Threaded mechanical splices which create a coupler designed to fail with sufficient energy dissipation Connectors between pre-cast concrete members Test coupler under varying parameters and loading conditions for energy dissipation performance Investigate tensile, compressive, and cyclic behaviors of the developed threaded mechanical splices
Shah and Moradi 2020 Steel plate fuses with butterfly shaped links so that shear and flexural yielding modes dominate the fuse behavior. Steel plate fuses may be used in a variety of steel frame configurations. Analyzes 3D finite element models using ANSYS Mechanical APDL software. Assess the sensitivity of the cyclic response of steel plate fuses having various design parameters.
Shahrooz, Fortney, and Harries 2018 Steel coupling beams consisting of a midspan fuse element that are embedded between the wall piers. This element is used to concentrate energy dissipation into the replaceable fuse, keeping the remaining elements from experiencing inelastic deformation. A specimen with a central core is coupled with steel coupling beams that are fixed with a fuse at the midspan of the beam. The fuse is 914 mm long on each beam, and wall and beam thickness was kept constant. A one-half scale specimen consisting of two walls and a coupling beam with a midspan fuse was subjected to two tests. The specimen was subjected to vertical displacement of one of the walls, then the fuse was replaced and it was subjected to 14% chord rotation. The fuse was found to be replaceable and to absorb most of the shear displacement. To test two midspan fuses in order to evaluate the performance of embedded beams with midspan fuses and to determine the replaceability of the midspan fuses.
Shao, Gu, Jia, Ge and Taguchi 2020 The brace-type shear fuse (BSF) is a metallic damper designed to avoid the limitations of traditional buckling-restrained braces (BRBs) and slit steel dampers (SSDs). The BSF has two shear units connected in series with each having a number of steel strips (eight in this experiment) connected in parallel. Middle bridging plates make these strips deform simultaneously and provide out-of-plane reinforcement. Small-scale specimens were tested quasi-statically to investigate how various parameters affect the mechanical properties of the BSF. A steel frame was evaluated to determine the seismic performance of buildings with BSFs. Determine if a proposed BSF improves upon conventional BRBs in practice.
Shen et al. 2011 Nonlinear replaceable link concept allowing a location of expected decoupled inelastic action Steel MRF with nonlinear replaceable links located away from the beam-column connection Full-scale testing of two different replaceable link connections is examined and an finite-element model is developed for comparison of behavior Experimentally validate the behavior of a nonlinear replaceable links as an alternative to traditional MRF beam-column connections
Smith and Willford 2007 Damped outriggers were inserted between perimeter columns and the ends of stiff outrigger elements cantilevering from the core as a new design philosophy for high-rise buildings The damper provides energy dissipation across the structural discontinuity of the core-to-perimeter column outrigger system A steady-state force response analysis was conducted as well as wind tunnel high-frequency force balance measures for the design example Design procedures, approaches and an example for damped outriggers is presented for the design of high-rise buildings
Valente et al. 2011 The Braced Ductile Shear Panel (BDSP) system provides energy dissipation through four concentric X-braces in series with a yielding rectangular ductile shear panel The bracing system is designed to be used as a retrofit or within new design for MRF and concentrically braced frames A model was created to evaluate the BDSP system behavior and a frame model was developed for global system evaluation Assess the effects of the BDSP system as a retrofit measure and analyze the behavior of the system analytically under seismic loading
Wang, Zhao, Gao, and Meng, 2020 Modular energy dissipation units for use in steel braces or frames. Modular energy dissipators placed at connections of steel members. Low cycle loading of seven test dissipators was performed, and modular dissipators displayed axial strain up to 4% prior to failure. To compare a modular energy dissipating unit to a nonmodular energy dissipating unit.
Xin Yan, M Shahria Alam, Ganping Shu, Ying Qin, 2023 A Self-centering viscous damper (SCVD) consists of two systems: a viscous energy dissipation system and a disc spring self-centering system. Disc springs connected in series were tested in compression Components of the SCVD were tested individually and as an integral damper to investigate peak deformation, residual deformation, and peak floor acceleration Explore improvements in seismic resilience of structures by offering high flexibility in load resistance, deformability, energy dissipation
Aghlara and Tahir, 2018 Bar fuse dampers consisting of inner and outer square tubes bolted together within round steel bars. Bar fuse dampers are placed within diagonal or chevron braces of a frame. Full scale specimens under monotonic and cyclic loading indicated that energy dissipation was performed by bar fuse dampers. To experimentally validate the use of bar fuse dampers under seismic loading and determine key parameters such as bolt configuration and bar diameter.
Aghlara, Tahir and Adnan 2018 The Pipe-Fuse Damper (PFD) is a passive damper designed to provide sufficient energy dissipation while also demonstrating stable hysteretic behavior. A PFD is comprised of a rigid inner and outer part connected via a flexible fuse part. Both cyclic and monotonic tests were conducted on specimens with differing number of pipes, and various diameters, lengths and thicknesses. Evaluate and improve the energy dissipation capabilities during seismic activity response of structures using a PFD.
Ai-lin, Ran, Zi-qin, and Zhen-yu, 2018 A circular column section attached to a cantilever beam is bolted to the independent beam section through a replaceable flange cover plate. Subassemblies of beam to column connections. Six subassemblies were tested under cyclic loading using a standard loading procedure until failure or a drift angle of 0.05 radians. To assess the seismic behavior and repairability of the prefabricated beam-column steel connections.
Meng Wang, Shunyu Zhang, Yi Sun, Kunpeng Dong Steel frames equipped with replaceable connections that are made of low yeild point steel The LYP steel connections were attached along beams near, but away from critical beam to column connections in a three story frame Six steel connection configurations were tested to determine which was the most optimal in achieving a two-step design target Low yield point (LYP) steel connection components are studied in their ability to control damage, along with its ability to be replaced after an earthquake.
Specimen Information

Reference Test/Analytical Setup Test Load Conditions Description of Fuse(s) Replaceable Self-Centering System Conclusions
Aliaari and Memari 2007 Series of 11 tests; 4 tests on the bare fame, 5 tests on frame with fuse elements, and 2 test on pinned frame with fuse elements Each test consisted of incrementally increasing displacements at the third floor level (displacement control) A lumber disk element was selected over a concrete or steel disk due to it increased ductility and its slower load resistant deterioration rate Yes, through specific small access window with the ability to replace the whole element as a component or an individual part No Experimental results show the SIWIS system works well as a seismic fuse system for infilled frames to save the infill walls from damage, but further experimental studies are needed to understand the system performance under cyclic loading
Bozorgzadeh et al. 2008 Shear keys were built at 1:2.5 scale of a prototype abutment in a five series test designed to simulate exterior shear key-bridge superstructure interaction Each key was loaded by two horizontal 980 kN compression capacity hydraulic actuators and displacement controlled cycles with increasing amplitude were run in three cycles Shear keys designed with smooth construction joints and limited vertical reinforcement No No An analytical model was developed to assist in designing the appropriate vertical reinforcement to induce sliding shear failure and a series of construction guidelines were created
Calado, Proenca, Espinha, and Castigloni 2013 Three subassemblies are produced with different free buckling lengths and tested with four different fuses. Cyclic and monotonic loading are applied to each subassembly, and force and top displacement are measured. Steel plates are bolted to the web and bottom flanges and are located in a gap in the slab. Yes, through bolted connections. No The steel fuse was replaceable and dissipated seismic energy through deformation, therefore limiting the plastic deformation at the beams.
Chen, Su, and Tang 2011 A model of a 14-story R/C building with the dampers was created using SAP2000 Displacement controlled cyclic tests were conducted on the damper Three-pin steel dampers are always in pairs and connected using pins providing easy manufacturing and avoidance of weld quality issues Yes No The three-pin damper exhibited stable behavior with large hysteretic loops and the analytical model showed the damper provided an effective reduction in seismic response
Crisafulli and Restrepo 2003 Two stiff framed steel plates with two connecting perforated steel plates were mounted in a 250 kN screw driven INSTRON universal testing machine Steel plates were tested under reverse cyclic shear forces and specimens was tested under cyclic lateral loading Perforated steel plates with a width approximately 1.6 times the diameter of the hole (test specimen: 250 wide x 80 deep x 10 mm thick; 50 mm diameter hole) No No Results show the design is adequate for shear in vertical joints, functions with excellent ductile displacement capacity without strength or stiffness degradation, and had advantages of simplicity over other proposed connecting devices with the same object
Dicleli and Mehta 2009 Single story frames and multistory frames (2 and 4) nonlinear static pushover, time-history and damage analyses were conducted A set of seven scaled ground motions were simulated HP section, which is composed of stocky plates capable of undergoing large inelastic lateral deformations; retrofitting requires cutting braces from gusset plate and attaching fuse Yes No RCBF exhibits a more stable and desirable lateral force-displacement relationship, a more stable behavior over a wide range of structural and ground motion properties, and less damage and larger reserve lateral deformation capacity compared with the CBF
Farrokhi, Danesh, and Eshghi 2009 Three full scale models were fabricated using a T connection with the column aligned horizontally and mounted on a reaction frame A saw tooth load pattern was implemented to account for the cyclic degradation phenomena Cover plates with drilled holes No No It was found the drilled holes shift the stress concentration from the connection face through the cover plates, and may eliminate the unfavorable brittle cracking mode of the weld roots and enhance the structural performance and reliability
Filipov et al. 2011 An analytical model was created in OpenSees and incorporates linear elastic behavior for all elements Varying superstructure and substructures were modeled using several suites and intensities of ground motions L shaped retainers designed as fuse components to fracture the attached anchor bolt under seismic motion Potentially, more research needed No Initial results show bearing friction force has a large influence on the superstructure displacement in the transverse direction and the abutment back wall tends to limit longitudinal displacements
Fortney, Shahrooz, and Rassati 2007 Coupling beams were embedded in wall piers and connected with a fuse system consisting of a slip critical web and flange splice connection Specimens were loaded with sets of increasing amplitudes of reverse cyclic force or displacement followed by one cycle of decreased amplitude to capture stiffness degradation Fuses are designed to have a shear capacity equal to the design shear with outer sections having sufficiently greater design shear to ensure they remain in the elastic range Yes, through bolted connection No The FCB set up led to early energy dissipation and lower stiffness relative to the SCB and it is recommended the fuse be designed for ultimate shear forces in order to withstand expected shear forces
Gray, Christopoulos, and Packer 2010 Full scale prototype was designed, manufactured and tested under axial stress representative of the stiffness of a buckling restrained brace A cyclic, quasi-static axial loading was induced with a universal testing machine Ductility of the yielding element is maximized by shaping the fingers to induce flexural yielding along most of their length No No Experimental results of an axial test of the CSF-brace assembly prototype confirmed the expected stiffness and ductility response of the device which closely matched analytical predictions
He, Chen, Eatherton and Shao 2018 Three full scale sub-assemblies with beam-to-composite connections were tested with two angles: reduce section angles and end-reinforced angles. The sub-assemblies were subjected to various cyclic tests. Energy dissipation is provided by replaceable FUSEIS (Fuse Innovative Systems) beams. Yes No The proposed connection can concentrate most of the damage in in easily replaceable angles on the lower flange.
Iqbal 2006 Shear keys were built at 1:2.5 scale of a prototype abutment in a five series test designed to simulate exterior shear key-bridge superstructure interaction Each key was loaded by two horizontal 980 kN compression capacity hydraulic actuators and displacement controlled cycles with increasing amplitude were run in three cycles Shear keys designed with smooth construction joints and limited vertical reinforcement Shear keys designed with smooth construction joints and limited vertical reinforcement No An analytical model was developed to assist in designing the appropriate vertical reinforcement to induce sliding shear failure and a series of construction guidelines were created
Karydakis, Ionnides, and Vagias 2011 15 full scale test were performed using three groups of connecting beam elements: beams of similar section, bars and rods, and beams of variable cross sections The elements were tested under cyclic loading The fuse element is created by expandable horizontal connections where plastic hinges are formed Yes No The system exhibited energy dissipation abilities and the experimental results were backed up by analytical numerical results from finite element analysis
Kasai et al. 2010 Full scale tested was conducted on the E-Defense Table of a 5-story steel MRF Excitations simulated were a DBE, maximum considered earthquake acceleration, the JR Takatori Ground Motions, and a 5% Damping Ratio Four dampers were considered: steel, oil, viscous, and viscoelastic Yes No The dampers provided significant energy dissipation, the buildings showed significantly less peak responses, and the story drift angle was within the 1% design target value
Kassis and Tremblay 2008 Single story steel building were laterally loaded at the roof level Full-scale quasi-static cyclic and dynamic seismic frame testing Fuse brace system consisting of structural tubing (rectangular or square) which is located near brace end No No The proposed fuse design behaved with reduced tension forces and stable hysteretic response and it is noted marked strain hardening response was observed and must be considered in capacity design check
Ke, Chen, Zhou, Yam, Hu, 2023 Specimen in a horizontal position and a 2000 kN hydraulic jack connected to the channels, includes a lateral bracing system with a self-equilibrium frame secured on strong floor Three stages of cyclic loading protocols at two cycles for each amplitude until failure is observed A new brace-type hybrid damper (BTHD) with steel slit plates that utilizes one of two friction mechanism sequences as proposed Yes No The test overall proved that the hybrid energy dissipation mechanism in the novel damper effectively enhanced the energy dissipation capacity and ductility compared to conventional steel slit plate dampers which is further validated by the numerical studies.
Kim, Choi, and Min 2010 Analytical models, consisting of 3,6 and 15-story reinforced concrete moment frames designed as ordinary MRFs and Special MRFs, were modeled using OpenSees An artificial earthquake with peak ground acceleration equal to 0.5 g was generated Composed of a central steel plate, two side plates and two circular friction pad discs placed in between the steel plates, which is all attached to an inverted pretension V-brace Yes and able to be retrofitted in structure No Nonlinear dynamic time-history analysis results showed that the structures retrofitted with rotational friction dampers generally satisfy the given performance objectives against seismic load
Krstulovic–Opara and Nau 2003 HPFRC fuse zones were modeled based off SIMCON and implemented into FEM The fuse was fixed along one side while the load was applied across a rigid steel plate on the opposite side HPFRC fuse zones are positioned in areas of high ductility such as beam end zones Yes, by means of bolted connections to adjacent members No The experimental SMA-HPFRC fuses demonstrate different structural response from conventional systems, but provided self-actuating concentrated energy absorptions zones which can be replaced
Legeron, Desjardins, and Ahmed, 2014 Four structures were tested: one HDF with a 5kN yield strength, one HDF with a 10 kN yield strength, one with elastic fasteners, and one free rocking system. They were subjected to a shake table test after performing a static load test. Static load testing was first used on the HDF1 structure by applying monotonic tensile and cyclical loading. Shake table tests were performed on the four structures using data from El Centro-NS and Kobe-NS. The shake table tests used a range from a 40% to 120% scale of the two earthquakes to test the structures. Hold downs equipped with a fuse function included a steel plate with slits cut into it to act as the fuse. The fuses were shaped into a butterfly pattern. A pair of fuse steel plates were welded to a U shaped steel channel. This structure was then inserted into a steel channel of a steel wall with self drilling screws and connected to an anchor bolt. Yes No It was found that the system dissipated energy through plastic deformation of the HDF such that the building's rocking behavior would dissipate the seismic energy. Structures with an HDF demonstrated the smallest base shear, and uplift deformation.
Lin, Chen, Yan, and Hu, 2020 Eleven models were tested against a displacement controlled cyclic loading test upon the T joint. The specimen included one mild steel joint, one high strength steel joint, and nine high strength steel joints with different fuses. An actuator performed the cyclic load test until fracturing or when the gap in the T joint closed. An actuator increased the applied magnitude of the drift ratio after every two identical cycles, starting at 0.25% and ending at 6%. Loading was terminated after the joint gap was closed or when fracturing was apparent. Nine different fuses were used, including different thicknesses, and different geometries. The different fuses included arc plate, slot plate, flat plate, strengthened flat plate, and buckling partially restrained plate. Yes No The shapes of the fuses had little influence on the seismic behavior of the T joints, but increase in thickness of the plate improved seismic performance. Strengthening the fuse plate or installing a buckling plate did increase the deformation capacity as well.
MacRae 2008 --- --- SHJ system- energy dissipation occurs in slip between beam and bottom flange plate; DSFD system- energy dissipated through bolted floating plate within braces SHJ - No, DSFD - Yes No SHJ connection provides adequate seismic performance and has been used in construction of NZ buildings and the DSFD provides advantages over ordinary BRB including no significant frame damage and are replaceable
Mansour, Christopoulo, and Tremblay 2011 Component test for ductility capacity and full scale testing of the first story EBF assembly of a 5-story EBF were conducted Link specimens were tested in shear and reverse moment curvature, and the full scale assembly was tested under cyclic shear deformations First link was a W-section welded to unstiffened end plates and the second was two channel sections back-to-back with a welded or bolted connection Yes No The link specimens were all found to achieve at least 0.08 rad plastic link rotation and the EBF with shear links was shown to transfer 14% more shear than the bare steel link and maintain the ability to be replaced with as much as 0.05% drift
Milani, Dicleli, 2022 Lateral supports, actuator, 1/3rd scale Chevron braced frame with specimen, loading apparatus and 50-ton reaction frame. Fully-reversed cyclic displacement with increasing amplitudes of 5.00 mm-intervals with at least 3 cycles at each amplitude Cylindrical yielding elements (CYEs) with the shape of a cylinder with enlarged ends made of ductile steel Yes No Experimental and numerical tests verified the new Torsional Hysteretic Damper for Frames (THDF) as an effective energy-dissipating device with high seismic performance via improving story drift distribution and reducing residual damage.
Ozaki, Kawai, Kanno, and Hanya, 2012 Eight different cross braced frames were fabricated. The test specimens had different configurations of the test fuse. The loading protocol of the specimens consisted of a common loading protocol of 150 kN in cyclic shear force designed to evaluate bolt displacement, followed by cycles of 2, 3, 4, and 5 times the yield displacement until system failure. A fuse was designed to carry the seismic loading of the bracing system in tension without reducing compressional strength. The fuses are placed at the diagonal connections of the cross bracing to limit bracing deformation. No No It was found that increasing the number of fuses in the system would decrease compressional strength but increase the tensile strength, and that the design requirements were all fulfilled with the fuse system installed and allowed for a reduction in brace volumes.
Ozaki, Kawai, Tanaka, Okada and Kanno 2010 A peak-to-peak alternative horizontal load was applied systematically to the top left of the shear wall until the fuse panels fractured. HDFFs were subjected to statically loaded experiments. Energy dissipation is provided by bisymmetrical rhomboid slits and is maximized by working forces and deformations concentrated in the HDFFs. Yes No HDFFs possess high plastic deformability and large energy absorbing capacities so it is considered to offer high seismic performance.
Patro and Sinha 2008 Linear behavior of the structure with friction devices is assumed and verified at both stick and sliding stage of response Nine ground motions were recorded on different soil conditions and used to evaluate the frame Friction energy-dissipation devices with slotted bolted connections, where the sliding plate within the vertical plane is connected to the centerline of the beam soffit No No Behavior of actual friction is more complex than the typical designs based on Coulomb friction, realistic friction model may alter effectiveness of present practice, and optimum pre-stress force may be very different for different response quantities
Qu, Liu, Hou, and Qiu 2018 Three full scale sub-assemblies with beam-to-composite connections were tested with two angles: reduce section angles and end-reinforced angles. The sub-assemblies were subjected to various cyclic tests. Energy dissipation is provided by replaceable FUSEIS (Fuse Innovative Systems) beams. Yes No The proposed connection can concentrate most of the damage in in easily replaceable angles on the lower flange.
Rai and Wallace 1998 1:4 scale models were created with varying section dimensions, two different alloys of aluminium (3003 and 6061), and arrangements of transverse stiffeners Cyclic load tests were conducted with varying frequencies Aluminium beam shear-links which dissipate energy through yielding in shear mode Yes, and retrofitting capabilities No The experimental testing showed the links ability to dissipate significant amounts of energy and the numerical results showed the shear-link braced frame had many seismic performance enhancements
Ruangrassamee and Mounnarath 2008 Thickness and gap size were varying parameters under tensile test, compressive test, and cyclic test Test were performed under the displacement control mode for monotonic tension testing and under two cycles per a specified max deformation for compressive and cyclic test Composed of hollow steel coupler threaded throughout its length and two reinforcing bars with threads at their ends Yes, repair at a connection will be simplified by replacing couplers No Load resistance is controlled by the coupler thickness while its ductility is controlled by gap lengths, splice exhibits higher resistance in compression after buckling, and energy dissipation increased in the cyclic test as the gap length increased
Shah and Moradi 2020 32 finite element models having different combinations of design parameters were analyzed. Fuses were subjected to incrementally increasing symmetrical cyclic drifts. Energy dissipation is provided by the butterfly shape of the slits in the steel plate. Yes No Fuse end-width, thickness and length have the most significant impact on the cyclic response of the steel plate fuse.
Shahrooz, Fortney, and Harries 2018 A one-half scale model of two concrete walls connected with a steel coupling beam that was fixed with a midspan fuse. One wall remained fixed in the first test while the other experienced vertical displacement until a maximum chord rotation of 2%. Then, the fuse was replaced and the maximum chord rotation was increased to 14%. A midspan fuse with a spring element to aid in energy dissipation was fixed at the center of the coupling beams. Yes -- The fuse reached its deformation capacity prior to the coupling beams, and the hysteretic responses of the system before and after replacing the fuse were similar, indicating that this model is a viable alternative to one without a fuse.
Shao, Gu, Jia, Ge and Taguchi 2020 Five specimen of varying heights (H) and widths (B) were tested. A two-dimensional six-story steel frame was also analyzed The five specimen were tested in an MTS testing system with a load capacity of 500kN and a deformation capacity of  75mm. The steel frame was subjected to a time history analysis. Energy dissipation is provided by the plastic yielding of steel strips under combined shear and bending. Yes No The proposed brace-type shear fuse (BSF) provided sufficient energy dissipation capacity and ductility. The lengths and widths of the steel strips also had a significant effect on strength and stiffness. The BSF greatly reduced both residual story drifts and maximum inter-story drifts.
Shen et al. 2011 Four full-scale assembly tests were performed on the beam-column assembly with replaceable links representing a first floor exterior connection Cyclic loading test were conducted until specimen limitations W-sections with endplates connections and back-to-back channels with bolted web connections Yes No MRF with nonlinear replaceable links provided adequate strength and ductility and end-plate links showed greater energy dissipation capacity than the bolted web links
Smith and Willford 2007 Direct analytical solutions obtained from ‘complex modal analysis’ and ‘harmonic forced response analysis’ and wind tunnel processing was performed for a 400m high tower Analytical response measured Displacement vs. Frequency and wind tunnel processing measured Peak Acceleration and Overturning Moment vs. Period of Oscillation Damping system described principally to reduce dynamic wind-induced response, but may be suitable for seismic response after appropriate non-linear history analyses No No The described design procedure for a damping outrigger system has economic advantages, provides increased damping and stiffness, and results in a favorable response to cyclic motion
Valente et al. 2011 An finite element model of the brace was developed using ABAQUS and an analytical model of a 6-story steel frame was developed using SAP2000 Fully reversed displacement cycles were applied the analytical model of the system and a nonlinear dynamic analysis was used to evaluate the analytical frame model Ductile shear panel composed of non-slender in-plane plate elements and stiffened by boundary flanges Yes No The study provided a global analysis for the BDSP system which decreased maximum top displacements in the frame and reduced plastic demands of the structural elements under seismic activity
Wang, Zhao, Gao, and Meng, 2020 The test fuses were loaded in a hydraulic servo universal testing machine and fixed using hydraulic clamps. Low cycle cyclic loading was applied to the test specimens up to a 4% axial strain. Yielding segments combined in series through threaded connections and contained within a restraining tube. Yes --- The modular energy dissipating units displayed axial deformations up to 4% prior to failure without significant strength reduction.
Xin Yan, M Shahria Alam, Ganping Shu, Ying Qin, 2023 Cyclic loading tests performed on self-centering system to ensure feasibility of applying preload, and the maximum internal friction was measure. A fabrication process and pre-compression procedure was suggested for the proposed for the SCVD N/A No Yes Disc springs displayed low capacity for energy dissipation and adequate self-centering capability
Aghlara and Tahir, 2018 The fuse component of the bar-fuse damper is placed vertically into a testing mechanism with a load cell on top and an actuator on the bottom. Displacement-controlled cyclic loading was performed with two cycles at each step. A bar-fuse damper consisting of a round steel bar containing two bolted square tubes in its center. Yes No The bar-fuse damper specimens effectively performed energy absorption and dissipation functions.
Aghlara, Tahir and Adnan 2018 Four full scale PFDs were subjected to various component tests. Specimens were tested cyclically and monotonically using an INSTRON machine. Flexural plastic deformation of the steel pipes provided the energy dissipation. Yes No The proposed PFD does have the capacity to act as an energy dissipating fuse in structures.
Ai-lin, Ran, Zi-qin, and Zhen-yu, 2018 An actuator is used to apply a load on the beam of 6 different full scale beam-column subassemblies. Displacement-controlled cyclic loading was applied at incremental story drift ratios. Bolted beam connections with a dog-bone flange cover plate in which a gap is included to allow rotation. Yes No Energy dissipation in the system was achieved through frictional damping of brass friction plates and plastic deformation of the flange cover plates.
Meng Wang, Shunyu Zhang, Yi Sun, Kunpeng Dong Six three story frames with different LYP steel connections configurations (bolted and welded connections) were tested Numerical simulations were used, along cyclic loading tests were performed on steel frames with different connection configurations using the LYP steel Low yield point steel connections configurations that comprised of bolted cover plates and T-stubs were tested in its ability to dissipate energy and localize damage, along with ability to be replaced Yes No LYP steel connections provide sufficient load carrying capacity, along with desirable deformation and dissipation capacity